P/N I-NX6V2-IM • REV C • ISS NOV12 NX-6V2 Control Panel Installation Manual

Pagina 2

Chapter 1: Reporting codes 6 NX-6V2 Control Panel Installation Manual Module list Table 3 below shows some of the modules that are compatible with th

Pagina 3 - Content

NX-6V2 Control Panel Installation Manual 7 Chapter 2 Programming Summary This chapter provides basic programming instructions and a description of

Pagina 4 - Important information

Chapter 2: Reporting codes 8 NX-6V2 Control Panel Installation Manual Location 44 - Duress code 36 Locations 45 to 50 - Auxiliary outputs program

Pagina 5 - Introduction

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 9 LED keypad programming This section describes how to program the address of e

Pagina 6 - NetworX

Chapter 2: Reporting codes 10 NX-6V2 Control Panel Installation Manual LED Keypad feature enabled 8 Enable multiple partition viewing. Enable tempor

Pagina 7 - Board installation

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 11 System clock To set the system clock: 1. Enter *, 9, 7, master code. The Se

Pagina 8 - T1 T R R1

Chapter 2: Reporting codes 12 NX-6V2 Control Panel Installation Manual assigned authority levels to all user numbers, or you can press # to exit a

Pagina 9 - Terminal descriptions

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 13 To enter program mode: 1. Press *, 8. The five function LEDs (Stay, Chime,

Pagina 10 - Module list

Chapter 2: Reporting codes 14 NX-6V2 Control Panel Installation Manual You are now ready to enter another programming location. If you attempt to p

Pagina 11 - Programming

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 15 Feature selection data Feature selection data displays the current condition

Pagina 12 - Chapter 2: Reporting codes

Copyright © 2012 UTC Fire & Security Americas Corporation, Inc. Interlogix is part of UTC Climate Controls & Security, a unit of United

Pagina 13 - LED keypad programming

Chapter 2: Reporting codes 16 NX-6V2 Control Panel Installation Manual a siren or bell is attached to the NX-6V2, it sounds for about 1 second. If th

Pagina 14 - Elapsed increments

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 17 Programming locations This section describes all the programming options for

Pagina 15 - User authority level

Chapter 2: Reporting codes 18 NX-6V2 Control Panel Installation Manual Caution: A call-waiting cancel on a non call-waiting line prevents successful

Pagina 16 - Control panel programming

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 19 Data Format Description 11 4+2 express Two-digit event code DTMF transmis

Pagina 17 - Chapter 2: Reporting codes

Chapter 2: Reporting codes 20 NX-6V2 Control Panel Installation Manual Location 4 - Phone 1 events reported Location 4 has two segments of feature se

Pagina 18 - Programming data types

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 21 • Enter 11 for a *, and 12 for a #. • Enter 14 to indicate the end of the

Pagina 19 - Loading factory defaults

Chapter 2: Reporting codes 22 NX-6V2 Control Panel Installation Manual • If you want dual or split reporting and the split is based on the event ty

Pagina 20

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 23 Location 13 - Phone 3 account code Location 13 has six segments of numerical

Pagina 21 - Programming locations

Chapter 2: Reporting codes 24 NX-6V2 Control Panel Installation Manual Segment 1 1. Alarms and alarm restores. 2. Opening and closings. 3. Zone byp

Pagina 22

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 25 Segment 1 1. On for 1800 Hz transmit; off for 1900 Hz. 2. On for 2300 Hz

Pagina 23

NX-6V2 Control Panel Installation Manual i Content Important information ii Chapter 1 Introduction 1 Product overview 2 Board installation

Pagina 24

Chapter 2: Reporting codes 26 NX-6V2 Control Panel Installation Manual Segment 1 1. On enables two call answering machine defeat. 2. On enables t

Pagina 25

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 27 Locations 23 and 24 - Partition features Location 23 - Feature report select

Pagina 26

Chapter 2: Reporting codes 28 NX-6V2 Control Panel Installation Manual Location 24 - Entry/exit times Location 24 has six segments of numerical data.

Pagina 27

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 29 Zone type Description 6. Instant Creates an instant alarm whenever it is tr

Pagina 28

Chapter 2: Reporting codes 30 NX-6V2 Control Panel Installation Manual Zone type Description 21. Gas detection Creates an instant alarm regardless o

Pagina 29

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 31 Location 25 - Zones 1 to 8 zone type Location 25 has eight segments of numer

Pagina 30

Chapter 2: Reporting codes 32 NX-6V2 Control Panel Installation Manual Location 37 - Siren and system supervision Location 37 has seven segments of f

Pagina 31

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 33 5. On will not allow zones that are force armed to report bypass. 6. Reserv

Pagina 32

Chapter 2: Reporting codes 34 NX-6V2 Control Panel Installation Manual Segment 4 - Siren time in minutes, 1 to 254. Default is 8. Segment 5 - Teleph

Pagina 33

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 35 Location 41 - Special features Location 41 has one segment of feature select

Pagina 34

ii NX-6V2 Control Panel Installation Manual Important information This is the NX-6V2 Control Panel Installation Manual. This document includes an

Pagina 35

Chapter 2: Reporting codes 36 NX-6V2 Control Panel Installation Manual Note: All segment 2 features must be on for the go to program code to be use

Pagina 36

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 37 Location 48 - Auxiliary output 2 event and times Location 48 has two segment

Pagina 37 - Location 40 - System timers

Chapter 2: Reporting codes 38 NX-6V2 Control Panel Installation Manual 16 = Autotest a 17 = Alarm memory 18 = Entry 19 = Exit 20 = Entry or exit 21 =

Pagina 38

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 39 Segment 1 Program the autotest interval. Enter 0 if the interval is in day

Pagina 39

Chapter 2: Reporting codes 40 NX-6V2 Control Panel Installation Manual Segment 2 - Program the minutes after the hour of the closing/autoarm time.

Pagina 40 - Location 44 - Duress code

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 41 Location 56 Restore communicator code Program the event code for any zone

Pagina 41

Chapter 2: Reporting codes 42 NX-6V2 Control Panel Installation Manual Location 72 Telephone line cut/restore communicator code Program the digits

Pagina 42

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 43 Location 84 - Daylight saving time Location 84 has four segments of numerica

Pagina 43

Chapter 2: Reporting codes 44 NX-6V2 Control Panel Installation Manual Locations 92 to 109 - Reserved Locations 110 to 169 - Zone type characteristic

Pagina 44

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 45 Segment 3 1. On enables fast loop response (50 mS; off = 500 mS). 2. On ena

Pagina 45

NX-6V2 Control Panel Installation Manual 1 Chapter 1 Introduction Summary This chapter provides an overview of your NX-6V2 Control Panel, including

Pagina 46

Chapter 2: Reporting codes 46 NX-6V2 Control Panel Installation Manual Location Zone type Description Default 125 8 Feature selection 1, 13, 378, 0,

Pagina 47

Chapter 2: Reporting codes NX-6V2 Control Panel Installation Manual 47 Location Zone type Description Default 158 25 Alarm code 14 159 25 Feature

Pagina 49

NX-6V2 Control Panel Installation Manual 49 Chapter 3 Troubleshooting Summary This chapter provides product specifications and information to help

Pagina 50

Chapter 3: Reporting codes 50 NX-6V2 Control Panel Installation Manual General diagnosis Trouble conditions are diagnosed by viewing the detailed in

Pagina 51

Chapter 3: Reporting codes NX-6V2 Control Panel Installation Manual 51 3. The backup battery is shorted internally or is defective. Remove the ba

Pagina 52

Chapter 3: Reporting codes 52 NX-6V2 Control Panel Installation Manual The siren does not work. The control panel has a built in siren driver. If the

Pagina 53 - Troubleshooting

Chapter 3: Reporting codes NX-6V2 Control Panel Installation Manual 53 Voltage tables The following tables show normal values for control panel v

Pagina 54 - Trouble conditions

Chapter 3: Reporting codes 54 NX-6V2 Control Panel Installation Manual Specifications Operating power 16.5 VAC 40 or 50 VA transformer Auxiliary po

Pagina 55 - Chapter 3: Reporting codes

NX-6V2 Control Panel Installation Manual 55 Appendix A Reporting codes Summary This appendix provides tables for various events and transmissions as

Pagina 56 - Chapter 3: Reporting codes

Chapter 1: Reporting codes 2 NX-6V2 Control Panel Installation Manual Product overview The NX-6V2 Control Panel is a residential security and alarm s

Pagina 57 - Voltage tables

Appendix A: Reporting codes 56 NX-6V2 Control Panel Installation Manual Reporting fixed codes in Contact ID and SIA The NX-6V2 can report SIA level 1

Pagina 58 - Specifications

Appendix A: Reporting codes NX-6V2 Control Panel Installation Manual 57 Contact ID event SIA Description 121 HA Keypad panic (silent) a 137 TA Keyp

Pagina 59 - Reporting codes

Appendix A: Reporting codes 58 NX-6V2 Control Panel Installation Manual Reporting zone codes in Contact ID and SIA The NX-6V2 has the ability to repo

Pagina 60 - Appendix A: Reporting codes

Appendix A: Reporting codes NX-6V2 Control Panel Installation Manual 59 Reporting Ademco Contact ID transmissions The NX-6V2 has the ability to rep

Pagina 61

Appendix A: Reporting codes 60 NX-6V2 Control Panel Installation Manual Device numbers for reporting expander troubles The following tables list the

Pagina 62 - (Locations 110 to 169)

Appendix A: Reporting codes NX-6V2 Control Panel Installation Manual 61 Device Name Number 570E/580E Switch 3 on Device address 25 Switch 1 and 3

Pagina 63

Appendix A: Reporting codes 62 NX-6V2 Control Panel Installation Manual Zone ID or user ID hex digit for 4+2 formats Zone or user ID hex digits only

Pagina 64

NX-6V2 Control Panel Installation Manual 63 Appendix B Programming worksheet Summary This appendix provides a programming worksheet to check default

Pagina 65

Appendix B: Reporting codes 64 NX-6V2 Control Panel Installation Manual Programming worksheet Use the following worksheet to check location defaults

Pagina 66

Appendix B: Reporting codes NX-6V2 Control Panel Installation Manual 65 Loc. Description Default Setting 11 Partition reported to phone 2 Segment

Pagina 67 - Programming worksheet

Chapter 1: Reporting codes NX-6V2 Control Panel Installation Manual 3 Board installation Inside the metal enclosure, there are slots for board ins

Pagina 68

Appendix B: Reporting codes 66 NX-6V2 Control Panel Installation Manual Loc. Description Default Setting 23 Partition 1 feature selection Segment 1

Pagina 69

Appendix B: Reporting codes NX-6V2 Control Panel Installation Manual 67 Loc. Description Default Setting 37 Siren and system supervision Segment 1

Pagina 70

Appendix B: Reporting codes 68 NX-6V2 Control Panel Installation Manual Loc. Description Default Setting Segment 4 = Siren time (1 to 254). 8 (minute

Pagina 71

Appendix B: Reporting codes NX-6V2 Control Panel Installation Manual 69 Loc. Description Default Setting 3 = Aux output to stop timing upon user co

Pagina 72

Appendix B: Reporting codes 70 NX-6V2 Control Panel Installation Manual Loc. Description Default Setting Segment 2 = Minutes. after hour of closing/a

Pagina 73

Appendix B: Reporting codes NX-6V2 Control Panel Installation Manual 71 Loc. Description Default Setting 68 AC fail/restore communicator code 0,

Pagina 74

Appendix B: Reporting codes 72 NX-6V2 Control Panel Installation Manual Loc. Description Default Setting Segment 3 1 = Open/close 2 = Bypass 3 = Rest

Pagina 75

Appendix B: Reporting codes NX-6V2 Control Panel Installation Manual 73 Loc. Description Default Setting 114 Zone type 3 alarm event code 7 115

Pagina 76

Appendix B: Reporting codes 74 NX-6V2 Control Panel Installation Manual Loc. Description Default Setting 148 Zone type 20 alarm event code 7 149 Z

Pagina 77

NX-6V2 Control Panel Installation Manual 75 Glossary Abort In enabled, the NX-6V2 waits the number of seconds programmed in Location 40 prior

Pagina 78

Chapter 1: Reporting codes 4 NX-6V2 Control Panel Installation Manual Figure 3: NX-6V2 wiring diagram 1AUX 4(SMOKE +)3COM2COM4COMPOSCOMDATA5312AUX +Z

Pagina 79 - Glossary

Glossary 76 NX-6V2 Control Panel Installation Manual Automatic cancel/abort If enabled, the cancel and/or abort features are automatic (pressing t

Pagina 80

Glossary NX-6V2 Control Panel Installation Manual 77 Dual/split/multiple reports The NX-6V2 sends communication reports to three different phone

Pagina 81 - Glossary

Glossary 78 NX-6V2 Control Panel Installation Manual Fail to communicate The NX-6V2 illuminates the Service LED if a report fails to reach the ce

Pagina 82

Glossary NX-6V2 Control Panel Installation Manual 79 Manual test If programmed, the NX-6V2 performs a bell and/or communicator test when *, 4, 4

Pagina 83

Glossary 80 NX-6V2 Control Panel Installation Manual Swinger shutdown This feature allows a zone or zones to be automatically bypassed after a spec

Pagina 84

Glossary NX-6V2 Control Panel Installation Manual 81 Zone activity monitor This feature sends a report to the central station when a particular

Pagina 87

Chapter 1: Reporting codes NX-6V2 Control Panel Installation Manual 5 Terminal descriptions Table 2 below describes the terminals shown in the wir