TERMINAL DESCRIPTION
TERMINAL DESCRIPTION
1 Connect one side of zone 1 loop. The other side of loop to common terminal 2. Open or
short causes alarm.
2 Common (-) Terminal.
3 Connect one side of zone 2 loop. The other side of loop to common terminal 2. Open or
short causes alarm.
4 -9 See Terminal Drawing and repeat the above sequence for zones 3-8
10, 11, 12, 13 Connect keypad wires as follows; yellow to terminal 10, green to terminal 11, black to
terminal 12, red to terminal 13. 200 ft. maximum run with 22 gauge wire, 500 ft.
maximum run with 18 gauge wire. Home run cable to each keypad.
14(-) & 15(+) Siren driver output to speaker(s), (speaker rating should be 15 watt at 8 or 16 ohm, or
30/40 watt at 4, 8, or 16 ohms). If siren driver disable is selected in location 132, output
becomes voltage output, 12VDC, 1 Amp maximum load.
16(-) & 17(+) Smoke detector power 12VDC, 100 mA maximum (For those jurisdictions which allow the
Priority zone to be used with smoke detectors.)
18(-) & 19(+) Auxiliary power, regulated 12VDC, 500 mA maximum.
20 Earth Ground, connect to a cold water pipe or 6 to 10 foot driven rod.
21 & 22 AC input, connect a 16.5V 25 VA, Class II U.L. approved transformer (included).
T1 House Telephone Tip (Brown)
T Telephone Tip (Green)
R Telephone Ring (Red)
R1 House Telephone Ring (Gray)
Battery Leads Standby battery leads black(-) and red(+) connect to a 12VDC lead acid rechargeable
battery. Do not connect to a dry cell battery.
FUSE DESCRIPTION
FUSE # DESCRIPTION
F2 KEYPAD (1 AMP)
F3 SPEAKER / BELL (2 AMP)
F4 AUXILIARY / SMOKE DETECTOR POWER (1 AMP)