NX-1700E Card Reader
9
Segment 2 LED1 (Green) Options:
LED1 - "On" to follow Ready status of system. (Default is “On”)
LED2 - "On" to toggle with the open collector output activation. (Default is “On”)
LED3 - "On" if inverted.
LED4-8 Reserved.
Segment 3 LED2 (Red) Options:
LED1 - "On" to follow Armed status of system. (Default is “On”)
LED2 - "On" to toggle with the open collector output activation.
LED3 - "On" if inverted.
LED4-8 Reserved.
Segment 4 Reader Partition:
LED1 - "On" if reader is in Partition 1. (Default is “On”)
LED2 - "On" if reader is in Partition 2. (Default is “On”)
LED3 - "On" if reader is in Partition 3. (Default is “On”)
LED4 - "On" if reader is in Partition 4. (Default is “On”)
LED5 - "On" if reader is in Partition 5. (Default is “On”)
LED6 - "On" if reader is in Partition 6. (Default is “On”)
LED7 - "On" if reader is in Partition 7. (Default is “On”)
LED8 - "On" if reader is in Partition 8. (Default is “On”)
LOCATION 243 PROGRAMMING THE ZONES
(2 segments of numerical data)
Segment 1 Door Shunt Zone
Program the zone that will be monitored as a door for access control. This location must be programmed with a valid zone for monitored
access control functions to work properly. (Default is 0)
Additionally, this zone must be configured in the control panel as a Door Shunt zone by programming an unused Zone Type
Characteristic in locations 111-169 (Seg 4, Opt 4).
Segment 2 Request To Exit (RTE) Zone
Program the zone that will be monitored to signal an RTE. If this segment is programmed with a valid zone and the zone is faulted, the
reader will activate its onboard open collector output and send the RTE. (Default is 0)
Additionally, this zone must be configured in the control panel as an RTE zone by programming an unused Zone Type
Characteristic in locations 111-169 (Seg 4, Opt 3).
LOCATION 244 PROGRAMMING THE VARIOUS READER TIMERS
(4 segment of numerical data)
Segment 1 Scan Time
Enter the amount of time required to hold a card between beeps to activate the functions programmed in Location 0, Segments 2 and 3.
This timer is timed in 1/100-second increments from 0 to 2.55 seconds. (Default is 100 = 1 second).
Segment 2 Relay Active Time
Enter the amount of time the onboard open collector output is energized once activated. This timer is timed in 1-second increments from 0
to 255 seconds. (Default is 10 = 10 seconds).
Segment 3 Door Fault Warning Time
Enter the amount of time a monitored zone (see Location 243, Segment 1) must be faulted before sounding a warning (local buzzer). The
door fault warning is timed in 1-second increments from 0 to 255 seconds. (Default is 30 = 30 seconds).
Segment 4 Door Fault Alarm Time
Enter the amount of time a monitored zone (see Location 243, Segment 1) must be faulted before sending an alarm condition to the control
panel. The door fault alarm is timed in 1-second increments from 0 to 255 seconds. (Default is 0 = disabled).
LOCATION 245 RESETTING THE READER ADDRESS
(1 segment of numerical data) If it is necessary to reset the address of the reader, enter a 0 in this location.
This will cause the reader to cease functioning. If a card is scanned with the system in Program Mode, the reader will again
find an available address and set itself, beeping back to the user the address that was found as per the table on page 3. If the
system is not in Program Mode and a card is scanned at a reader with a reset address, then it will sound an error beep.